25.03.2010
ETCI TC2 (Electrical Installations) has recently issued notices relating to the National Rules for Electrical Installations, Fourth Edition:
Amendments to Fourth Edition - The latest list of amendments, corrigenda and errata list for the Fourth Edition, referenced 06/2009, can be accessed on the ETCI website (www.etci.ie).
Core colours - Some electrical installations may contain older wiring systems that do not comply with the colour code specified in the current National Rules. In such cases, it is necessary for safety reasons that warning notices be provided for the benefit of personnel who may not be familiar with the older systems. In some older installations, the colour black was used for the neutral conductor, and in three-phase circuits, the colour blue was used for a phase/line conductor.
TC2 advises that warning notices should be provided in the relevant locations, e.g. distribution boards, with the following wording or its equivalent: 'WARNING - The colours for cables and insulated conductors in this (part of the) installation do not comply with the National Rules for Electrical Installations ET 101: 2008. The core colours and their respective functions should be verified by measurement.'
|
Related contacts
|
Electro-Technical Council of Ireland (ETCI) Web: www.etci.ie |
| For latest electrical industry news, register for Voltimum's free newsletter. |
|
|
Source: James Hunt & ETCI |
|