NSX250N 4P 50kA Frame
NSX250N 4P 50kA Frame
- SKU
range of product: NSX100...250,NSX100...250
device short name: Compact NSX250N,Compact NSX250N
circuit breaker name: Compact NSX250N,Compact NSX250N
poles description: 4P,4P
neutral position: left,left
network type: AC,AC
network frequency: 50/60 Hz,50/60 Hz
[In] rated current: 250 A ( 40 °C ),250 A ( 40 °C )
[Ui] rated insulation voltage: 800 V AC 50/60 Hz conforming to IEC 60947-2,800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2,8 kV conforming to IEC 60947-2
[Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2,690 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity code: N,N
breaking capacity: Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2,Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2,Icu 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2,Icu 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2,Icu 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2,Icu 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2,Icu 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2,Icu 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2,Icu 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2,Icu 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2,50 kA at 480 V AC 50/60 Hz conforming to NEMA AB1,50 kA at 480 V AC 50/60 Hz conforming to NEMA AB1,50 kA at 480 V AC 50/60 Hz conforming to UL 508,50 kA at 480 V AC 50/60 Hz conforming to UL 508,20 kA at 600 V AC 50/60 Hz conforming to NEMA AB1,20 kA at 600 V AC 50/60 Hz conforming to NEMA AB1,15 kA at 600 V AC 50/60 Hz conforming to UL 508,15 kA at 600 V AC 50/60 Hz conforming to UL 508,Icu 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2,Icu 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2,85 kA at 240 V AC 50/60 Hz conforming to UL 508,85 kA at 240 V AC 50/60 Hz conforming to UL 508,90 kA at 240 V AC 50/60 Hz conforming to NEMA AB1,90 kA at 240 V AC 50/60 Hz conforming to NEMA AB1
[Ics] rated service breaking capacity: Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2,Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2,Ics 35 kA 525 V AC 50/60 Hz conforming to IEC 60947-2,Ics 35 kA 525 V AC 50/60 Hz conforming to IEC 60947-2,Ics 90 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2,Ics 90 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2,Ics 50 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2,Ics 50 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2,Ics 50 kA 440 V AC 50/60 Hz conforming to IEC 60947-2,Ics 50 kA 440 V AC 50/60 Hz conforming to IEC 60947-2,Ics 36 kA 500 V AC 50/60 Hz conforming to IEC 60947-2,Ics 36 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation: yes conforming to IEC 60947-2,yes conforming to IEC 60947-2,yes conforming to EN 60947-2,yes conforming to EN 60947-2
utilisation category: category A,category A
pollution degree: 3 conforming to IEC 60947-1,3 conforming to IEC 60947-1