MICROLOGIC CORD FOR USB INTERFACE
product or component type: circuit breaker
device short name: Compact NSX400N
circuit breaker application: distribution
poles description: 3P
protected poles description: 3t
network type: AC
network frequency: 50/60 Hz
[In] rated current: 400 A ( 40 °C )
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ue] rated operational voltage: 690 V AC 50/60 Hz
breaking capacity code: N
breaking capacity: Icu 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2,Icu 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2,Icu 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2,Icu 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2,Icu 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2,Icu 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2,85 kA at 240 V AC 50/60 Hz conforming to UL 508,85 kA at 240 V AC 50/60 Hz conforming to NEMA AB1,42 kA at 480 V AC 50/60 Hz conforming to NEMA AB1,50 kA at 480 V AC 50/60 Hz conforming to UL 508,20 kA at 600 V AC 50/60 Hz conforming to UL 508,20 kA at 600 V AC 50/60 Hz conforming to NEMA AB1
[Ics] rated service breaking capacity: Ics 85 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2,Ics 50 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2,Ics 42 kA 440 V AC 50/60 Hz conforming to IEC 60947-2,Ics 11 kA 525 V AC 50/60 Hz conforming to IEC 60947-2,Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2,Ics 30 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation: yes conforming to EN 60947-2,yes conforming to IEC 60947-2
utilisation category: category A
trip unit name: Micrologic 2.3
trip unit technology: electronic
trip unit protection functions: LSoI
trip unit rating: 400 A ( 40 °C )
protection type: short time short-circuit protection,instantaneous short-circuit protection,overload protection (long time)
pollution degree: 3 conforming to IEC 60664-1
Product identifiers
SKU: TRV00917
EAN: 3606480025501
GTIN: 3606480025501