200A 4P4d 36kA NSX250F TM-D
200A 4P4d 36kA NSX250F TM-D
- SKU
product or component type: circuit breaker
device short name: Compact NSX250F
circuit breaker application: distribution
poles description: 4P
protected poles description: 4t
neutral position: left
network type: AC
network frequency: 50/60 Hz
[In] rated current: 250 A ( 40 °C )
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ue] rated operational voltage: 690 V AC 50/60 Hz
breaking capacity code: F
breaking capacity: 35 kA at 480 V AC 50/60 Hz conforming to UL 508,35 kA at 480 V AC 50/60 Hz conforming to NEMA AB1,20 kA at 600 V AC 50/60 Hz conforming to NEMA AB1,15 kA at 600 V AC 50/60 Hz conforming to UL 508,Icu 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2,85 kA at 240 V AC 50/60 Hz conforming to NEMA AB1,85 kA at 240 V AC 50/60 Hz conforming to UL 508,Icu 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2,Icu 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2,Icu 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2,Icu 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2,Icu 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity: Ics 85 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2,Ics 8 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2,Ics 30 kA 500 V AC 50/60 Hz conforming to IEC 60947-2,Ics 22 kA 525 V AC 50/60 Hz conforming to IEC 60947-2,Ics 35 kA 440 V AC 50/60 Hz conforming to IEC 60947-2,Ics 36 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation: yes conforming to IEC 60947-2,yes conforming to EN 60947-2
utilisation category: category A
trip unit name: TM-D
trip unit technology: thermal-magnetic
trip unit protection functions: LI
trip unit rating: 200 A ( 40 °C )
protection type: overload protection (thermal),short-circuit protection (magnetic)
pollution degree: 3 conforming to IEC 60664-1