GTIN
range: TeSys product name: TeSys GV3 device short name: GV3L product or component type: circuit breaker circuit breaker application: motor protection poles description: 3P network type: AC utilisation category: AC-3 conforming to IEC 60947-4-1,category A conforming to IEC 60947-2 network frequency: 50/60 Hz breaking capacity: Icu = 50 kA at 400/415 V AC 50/60 Hz,Icu = 100 kA at 230/240 V AC 50/60 Hz,Icu = 50 kA at 440 V AC 50/60 Hz,Icu = 6 kA at 690 V AC 50/60 Hz,Icu = 12 kA at 500 V AC 50/60 Hz [Ics] rated service short-circuit breaking capacity: 100 % at 230/240 V AC 50/60 Hz,100 % at 400/415 V AC 50/60 Hz,100 % at 440 V AC 50/60 Hz,50 % at 500 V AC 50/60 Hz,50 % at 690 V AC 50/60 Hz trip unit rating: 40 A trip unit technology: magnetic magnetic tripping current: 560 A

Documents

User guide

TeSys Power - Deca Motor Circuit Breakers Frame 3 - Use in Explosive Atmospheres

Open

Instruction sheet

GV3 P../L.., GV3 P..6/L..6 - Everlink circuit breaker - Instruction Sheet

Open

Catalogue

TeSys - Catalog 2025 - Innovative and connected solutions for motor starters

Open

Environmental compliance declaration

GV3L40 China RoHS Declaration

Open

Environmental disclosure

TeSys Deca,3P,48-65A Motor circuit breaker

Open