1 / 5
MOTOR BREAKER 37-50A
1 / 5
MOTOR BREAKER 37-50A
- SKU
- EAN
- GTIN
range: TeSys
product name: TeSys GV3
device short name: GV3P
product or component type: circuit breaker
circuit breaker application: motor protection
poles description: 3P
network type: AC
utilisation category: AC-3 conforming to IEC 60947-4-1,category A conforming to IEC 60947-2
network frequency: 50/60 Hz conforming to IEC 60947-4-1
breaking capacity: Icu = 6 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2,Icu = 50 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2,Icu = 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2,Icu = 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2,Icu = 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity: 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2,50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2,100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2,100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2,50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
thermal protection adjustment range: 37...50 A
trip unit technology: thermal-magnetic
magnetic tripping current: 700 A
Documents
Environmental compliance declaration
GV3P50 REACh Declaration
TeSys Power - Deca Motor Circuit Breakers Frame 3 - Use in Explosive Atmospheres
Environmental compliance declaration
GV3P50 China RoHS Declaration
TeSys Deca,3P,48-65A Motor circuit breaker
TeSys Deca,3P,48-65A Motor circuit breaker